Specificatio |
Probe voltage: |
5 V AC |
Probe current: |
< 1 mA A |
Sensitivity Adjustable: |
from 5 kΩ to 100 kΩ |
Max. cable capacity: |
4 nF |
Response time: |
400 ms |
Setting accuracy: |
(mech.) ± 5 % |
ON / OFF switching delay: |
adjustable from 0.5 to 10 s |
Relay output: |
2x SPDT |
Switching voltage: |
250 V AC1, 24 V DC |
Switching current: |
16 A AC1 |
Switching power: |
4000 VA AC1, 384 W DC |
Electrical strength: |
4 kV |
Mechanical life-span: |
3 x107 switches |
Electrical life-span: |
0,7x105 switches |
Power supply: |
110, 230 V AC 24 V AC/DC |
Voltage range: |
allowed nominal voltage – 15% ... +10% |
Power consumption: |
max 4.5 VA |
Ambient temperature: |
from -20 °C to +55 °C |
Electrical connection: |
max. 2.5 mm² / with insulation 1.5 mm² |
Electrical protection: |
class II class III |
Ingress protection: |
IP 20 |
Mechanical connection: |
DIN EN 60715 rail |
Weight: |
72g |